YOUR PREFERRED PARTNER
SINCE 1981

PRIMARY VOLTAGE : 400 V | SECONDARY : 230 V WITH MIDPOINT

Options :
REACH_Compliance RoHS2_Compliant
Ref.
11
IP
Montage Rail Din
Power (kVA)
0,04
Primary terminals (mm2)
2,5
Secondary terminals (mm2)
2,5
Dimensions (mm) (W / H / D)
90 / 95 / 105
Mounting (mm) (w / d / hole diameter)
90 / 105 / 105
Core losses (W)
3
Copper losses (W)
3
Short-circuit voltage (%)
-
Weight (Kg)
1,8
Inrush current (In)
-

A medical environment requires the design of specific transformers.

Circé manufactures the medical IT isolation single-phase version with a midpoint on the secondary winding according to the standards associated to this product. The IT medical scheme is defined by the installation standards NFC 15211, CEI 60364-7-710 for premises where the patient's safety must not be compromised in case of an isolation fault. Medical transformers are low-voltage isolating transformers that provide separation between the general distribution network and the supply of IT-powered medical premises.

Compliance

Our single-phase medical transformers comply with the norms EN 60076-11 ou EN 61558-2-15 / EC marking / EMC compatible / REACH / ROHS 2.

Connection

Two types of connection exist depending on the power rating of the product :

- spring terminals,

- screw terminals.

Standard technical features

- Power rating: from 2.5 to 10 kVA

- Frequency: 50/60 Hz

- Dry-type with natural air cooling

- Lifting rings from 15 kg

- Electrostatic shield

- Temperature class F (45° environment)

- Altitude: up to 1,000m

- Short-circuit voltage < 3%

- Isolation voltage between windings: 3,550V

- Isolation voltage between windings and earth: 1,770V

- Reinforced isolation

- Temperature probes 160°/180°C

- Available without housing, with IP23 housing or other on request

- Inrush current < 12 In

Mounting drawing

Without housing (up to 5kVa)
Without housing (starting at 6,3kVA)
IP23 housing
This site uses cookies and gives you control over what you want to activate Accept all Personalize